Sign In | Join Free | My ecer.com.ru |
|
Brand Name : Invensys Triconex
Model Number : 3708E
Certification : COC
Place of Origin : USA
MOQ : 1 Piece
Price : inquiry
Payment Terms : T/T
Supply Ability : 10 Piece per a day
Delivery Time : 5-8 work days
Packaging Details : original
Name : 3708E Invensys Triconex Isolated Thermocouple Module
Model : 3708E
Package : STANDARD
Warranty : 12 months
Gross Weight : 2.2 lbs / 35.2 oz / 1kg
Packing Size : 7" x 7" x 4" (18 cm x 18 cm x 10 cm)
Lead time : 1~3 Days
Quality : 100%Brand
Product name : Isolated Thermocouple Module
Stock : Available
3708E Invensys Triconex Isolated Thermocouple Module
Product Details:
Brand Name | Invensys Triconex |
Model | 3708E |
Catalog | TMR architecture |
Origin | United States (USA) |
Dimension | 16*16*12cm |
Weight | 1kg |
HS Code | 8537101190 |
Payment | T/T |
Sales Price | $4000 |
Warranty | 12 months |
Lead time | 3-5 work days |
Description:
A thermocouple input (TC) module includes three independent input channels. Each input channel receives variable voltage signals from each point, performs thermocouple linearization and cold-junction compensation, and converts the result to degrees Celsius or Fahrenheit. Each channel then transmits 16-bit signed integers representing 0.125 degrees per count to the three main processors on demand. In TMR mode, a value is then selected using a mid-value selection algorithm to ensure correct data for every scan.
Each thermocouple input module is programmable to support one thermocouple type, selected from J, K and T for standard thermocouple input
modules and from J, K, T and E for isolated thermocouple input modules.
The isolated module allows users to select upscale or downscale burnout detection with the TriStation software.
For non-isolated modules, upscale or downscale burnout detection depends on the field termination selected. Triplicated temperature transducers
residing on the field termination panel support cold-junction compensation.
Each channel of a thermocouple input module performs auto-calibration using internal precision voltage references. On the isolated module, a faulting coldjunction transducer is annunciated by a cold-junction indicator on the front panel.
![]() |
3708E Invensys Triconex Isolated Thermocouple Module Images |